Battery Storage Sizer

Size your battery bank using autonomy, depth-of-discharge, and efficiency assumptions aligned with NREL REopt/SAM and IEC 61427-1 guidance.

Load & Autonomy

kWh/day

Average critical load to be backed up.

kW

Maximum instantaneous power draw.

days
kWh

Compare required vs installed capacity.

Battery Parameters

fraction
fraction
fraction

Accounts for lifecycle and climate.

ร—

Multiplier for startup/ motor loads.

hours

Target to recharge from PV/grid.

Calculate

๐Ÿ“– How to Use

Enter daily critical load, desired autonomy, and battery parameters (DoD, efficiency, derating). The calculator outputs the required DC nameplate capacity, power rating for charge/discharge, and state-of-charge window following IEC 61427-1 testing practices.

๐Ÿงฎ Formula Reference

Usable energy = Daily load ร— Days of autonomy
Nameplate capacity = Usable energy รท (DoD ร— RTE ร— TCF)
Duration = Usable energy รท Peak power
Charge power โ‰ˆ Nameplate รท Charge time

โš ๏ธ Notes

  • Keep DoD within manufacturer warranty limits to maintain cycle life.
  • Adjust temperature derate for extremes (e.g., โˆ’20ยฐC lithium may need 0.7 factor).
  • Include inverter AC/DC efficiency if sizing for AC loads.